Do I have to follow the prescriptive insulation table, or can I use REScheck, performance, or a HERS rating?
IRC 2018 Energy Code Compliance Paths Explained
Compliance
Published by Jaspector
Code Reference
IRC 2018 — N1101.3
Compliance · Energy Efficiency
Quick Answer
IRC 2018 Section N1101.3 allows three compliance paths for residential energy code: the prescriptive path using the 2018 IECC Table R402.1.2 minimum R-values and U-factors for each building envelope component; the total UA alternative (commonly called the REScheck path) where the building's total thermal conductance can meet or underperform prescriptive in some components if it exceeds prescriptive in others; and the Energy Rating Index (ERI) path where a certified HERS rater calculates an energy index score and the building achieves a maximum ERI value based on the climate zone. Most residential new construction uses the prescriptive path because it requires no energy modeling software. The REScheck path is used when design trade-offs between components are needed. The ERI path is used for high-performance and green-certified projects.
What N1101.3 Actually Requires
Section N1101.3 of IRC 2018 Chapter 11 states that the building thermal envelope must comply with sections N1102.1 through N1102.5 using one of the permitted compliance methods. The three compliance methods are the prescriptive compliance path from Table R402.1.2, the total thermal transmittance (UA) alternative from N1102.1.4, or the Energy Rating Index alternative from N1101.3.1.
The prescriptive path requires that each component of the building envelope individually meet the minimum performance values in the 2018 IECC Table R402.1.2 for the climate zone — specific R-values for ceilings, walls, floors, basement walls, crawl space walls, slab perimeters, and specific maximum U-factors and solar heat gain coefficients for windows and doors. Every component must simultaneously satisfy its own minimum standard. No trade-off between components is permitted on the prescriptive path — superior ceiling insulation does not compensate for a wall assembly that falls below the minimum R-value. The prescriptive path is simple to document and verify but offers no flexibility to trade off between building components.
The total UA alternative, implemented through the DOE REScheck software, allows the builder to deviate from prescriptive minimums in individual components as long as the overall building thermal performance equals or exceeds what would result from the prescriptive values. REScheck calculates the total UA (sum of U-factor times area for all envelope components) for the proposed building design and compares it to the total UA of an equivalent building meeting all prescriptive minimums. If the proposed building UA is equal to or less than the reference prescriptive UA, the building complies even if individual components are below prescriptive. This allows, for example, a builder to use more window area than the prescriptive limit allows by adding additional ceiling or wall insulation to offset the window UA increase. REScheck is free software from the DOE and is widely used by builders for designs that require component trade-offs.
The Energy Rating Index path requires a certified HERS rater to model the entire building using approved energy simulation software and calculate an ERI score. The maximum allowable ERI varies by climate zone — Zone 1 allows a maximum ERI of 52, Zones 2 through 4 allow 52, Zone 5 allows 52, Zones 6 through 8 allow 54. An ERI of 100 represents the performance of a reference building meeting the 2006 IECC minimum, so an ERI of 52 means the building uses approximately 48 percent less energy than the 2006 IECC reference. The ERI path allows maximum design flexibility because any combination of building features that achieves the required ERI score is compliant, including buildings with very high window area, non-standard insulation configurations, or high-efficiency mechanical systems offsetting reduced envelope performance. The ERI path requires third-party certification and is commonly used for Energy Star, DOE Zero Energy Ready, and LEED-certified projects.
Why This Rule Exists
Multiple compliance paths exist because residential construction is not uniform — different design approaches, site conditions, budget constraints, and performance goals require different compliance strategies. A simple ranch house on a standard lot with conventional framing and a vented attic is easily served by the prescriptive path. A house with a large south-facing window wall for passive solar benefit exceeds the prescriptive window area limits but may have superior overall energy performance due to solar gains — the REScheck path allows this design to demonstrate compliance by showing that the thermal envelope as a whole meets or exceeds the prescriptive UA baseline. A net-zero or ultra-low-energy house targeting maximum efficiency uses the ERI path to demonstrate that its combination of super-insulated envelope and high-efficiency mechanical systems achieves a far lower ERI than required, enabling design choices not explicitly permitted by the prescriptive table.
The availability of multiple paths also drives innovation in construction — if the only path were the prescriptive minimum, there would be no mechanism to incentivize builders to exceed the minimum through creative building assembly design. The ERI path creates a framework for performance competition that benefits occupants and the environment.
What the Inspector Checks at Rough and Final
The inspector verifies at permit review that the energy compliance documentation submitted with the permit application identifies the compliance path being used and provides the required supporting calculations. For the prescriptive path, the permit documentation typically includes a checklist or schedule showing the proposed R-values and U-factors for each component compared to the required prescriptive values. For the REScheck path, a printed REScheck compliance certificate showing the proposed and reference UA values and the passing result must be submitted. For the ERI path, the HERS rater provides an initial energy model report showing the projected ERI and the required field verification plan.
At final inspection, the inspector verifies that the energy certificate posted per N1101.14 accurately reflects the compliance path used and documents the as-built values. For ERI path projects, the HERS rater must provide a final rating certificate confirming the as-built ERI score after field inspections and blower door and duct leakage testing are complete. The final ERI certificate must be included with or attached to the energy certificate posted at the electrical panel.
What Contractors Need to Know
Choose the compliance path before permit application because the required documentation differs significantly between paths. The prescriptive path requires the least documentation — a simple schedule of proposed R-values and U-factors compared to the code table. The REScheck path requires a printed compliance certificate from the DOE REScheck software. The ERI path requires a qualified HERS rater to be engaged from the design stage, with both an initial energy model for permit submission and a final verified rating at project completion.
For projects using the REScheck total UA path, input all building components accurately into REScheck including all windows and glass doors with their NFRC-rated U-factors and SHGC values. An incorrect window U-factor entry can make a non-compliant design appear compliant in the software. The REScheck certificate submitted at permit must accurately represent the design as proposed and the as-built certificate must reflect the final installed values. If window or insulation specifications change during construction, the REScheck calculation must be updated to confirm continued compliance.
The ERI path is most cost-effective on projects that are already targeting green certifications such as Energy Star, DOE Zero Energy Ready, LEED for Homes, or National Green Building Standard ratings that require HERS rater involvement. The marginal additional cost to use the ERI compliance path on a project already receiving a HERS rating for green certification is minimal compared to the cost of engaging a HERS rater solely for code compliance.
What Homeowners Get Wrong
Homeowners often assume that passing the HERS rating and obtaining a green certification automatically means the home exceeds the code minimum. While HERS-rated homes are typically more efficient than code minimum, the ERI compliance path sets a maximum ERI value that must be achieved — a HERS rating number alone does not confirm code compliance unless it is at or below the maximum ERI for the climate zone. The HERS index and the ERI compliance threshold are related concepts but not identical — the HERS index is a continuous scale while the ERI maximum is a specific threshold required for code compliance.
Homeowners who want to verify their home was built to the adopted energy code can ask to see the energy compliance documentation submitted with the permit. For prescriptive compliance, they should see a component schedule showing all envelope R-values and fenestration U-factors compared to code minimums. For REScheck compliance, a printed compliance certificate should be on file. For ERI compliance, the HERS rater final rating certificate should be available. If this documentation was not submitted or is not on file, the compliance basis for the home is uncertain.
Homeowners planning additions or substantial alterations should understand that the IRC 2018 energy requirements apply to the new construction component of additions. If an addition triggers a full energy code review, the compliance path must be selected and documented for the addition scope, which may require REScheck or ERI analysis if the addition design does not conform to the prescriptive minimums for all components.
State and Local Amendments
IRC 2018 states including TX, GA, VA, NC, SC, TN, AL, MS, KY, and MO adopted N1101.3 and the three compliance paths through the 2018 IECC. Some states have preferences or requirements regarding which compliance software is acceptable for the UA alternative path — most accept DOE REScheck and some also accept state-developed compliance tools. The ERI path is accepted in all states adopting the 2018 IECC but the HERS rater must be certified by RESNET or an equivalent certification body recognized by the state. Note that IRC 2021 adopted the 2021 IECC, which retained all three compliance paths but updated the prescriptive values and reduced the maximum ERI thresholds in several zones, reflecting tighter energy performance standards. States adopting IRC 2021 will have lower maximum ERI scores required for ERI path compliance.
Some local jurisdictions have adopted stretch codes or reach codes that require performance above the base IRC minimum. In jurisdictions with stretch codes, the ERI path may require a lower ERI than the base IRC maximum. Verify local energy code requirements before selecting a compliance path and designing the building system.
When to Hire a Licensed Contractor
The prescriptive and REScheck compliance paths can be managed by the builder with support from an energy consultant for the REScheck software if needed. The ERI compliance path requires engagement of a RESNET-certified HERS rater from the design stage through final rating and documentation. HERS raters are independent third-party professionals who model, inspect, and certify building energy performance. For projects targeting Energy Star, DOE Zero Energy Ready, or LEED for Homes certification, a HERS rater is required by those certification programs regardless of which energy code compliance path is selected.
Common Violations Found at Inspection
- No energy compliance documentation submitted with the permit application — inspector cannot verify which compliance path was selected or whether the design meets the requirements.
- Prescriptive path used with one or more building components below the Table R402.1.2 minimum for the climate zone, without switching to the REScheck UA path to justify the trade-off.
- REScheck certificate submitted at permit uses assumed or design U-factor values for windows that differ from the NFRC-rated values of the windows actually installed, making the certificate inaccurate.
- ERI path used at permit but final HERS rating certificate not submitted at final inspection because the rater was not engaged to perform field verification.
- Energy certificate posted at final inspection documents the compliance path as prescriptive but the as-built construction includes components below prescriptive minimum that were not justified through a REScheck calculation.
- REScheck calculation not updated to reflect construction substitutions — original REScheck passes but field-installed window specifications reduced U-factor performance, making the original calculation non-representative of as-built conditions.
- Maximum ERI for the climate zone not confirmed — ERI path documentation submitted but the certified ERI score is above the maximum allowed for the project climate zone.
Frequently Asked Questions
FAQ — IRC 2018 Energy Code Compliance Paths Explained
- What is the difference between the prescriptive path and REScheck?
- The prescriptive path requires every building envelope component to individually meet the minimum R-value or U-factor in Table R402.1.2 for the climate zone — no trade-offs are allowed between components. REScheck uses the DOE total UA software to allow trade-offs between components as long as the overall building thermal performance equals or exceeds the prescriptive reference baseline. REScheck is used when design choices require one component to be below prescriptive and another to be above prescriptive to compensate.
- What HERS score is required to pass the ERI compliance path under IRC 2018?
- The maximum ERI under the 2018 IECC ERI path is 52 for Climate Zones 1 through 5 and 54 for Zones 6 through 8. A HERS index at or below these values satisfies the ERI compliance path. Note that the HERS index and ERI are related concepts — verify with the HERS rater that the certified ERI score qualifies for code compliance in addition to any green certification score.
- Can I use more windows than the prescriptive table allows if I add extra insulation?
- Yes — the REScheck total UA path allows increased window area above the prescriptive maximum if additional insulation in ceilings, walls, or other components brings the total building UA to the prescriptive reference level or below. Run the REScheck calculation with the proposed window area and the enhanced insulation levels to confirm the total UA comparison passes.
- What software is used for the REScheck total UA compliance path?
- The DOE REScheck software, available free from the DOE Building Energy Codes Program website, is the standard tool for the total UA alternative compliance path. Most jurisdictions accept REScheck output as the compliance documentation for this path. Some states also accept state-developed compliance calculation tools.
- Does using the ERI path mean the home automatically gets Energy Star certification?
- No. The ERI compliance path satisfies the minimum energy code requirement — it does not automatically grant Energy Star, LEED, or DOE Zero Energy Ready certification. Those certifications have their own requirements in addition to the ERI score. However, projects already pursuing those certifications through a HERS rater can often use the ERI compliance path at minimal additional cost since the rater is already engaged.
- What changed in IRC 2021 for energy compliance paths?
- IRC 2021 retained all three compliance paths but updated the prescriptive values in Table R402.1.2 and reduced the maximum ERI thresholds in several zones to reflect tighter performance standards. States adopting IRC 2021 will have stricter prescriptive minimums and lower maximum ERI scores required for ERI path compliance compared to IRC 2018.
Also in Energy Efficiency
← All Energy Efficiency articles- Basement Wall Insulation Under IRC 2018 Energy Code
Do basement walls need insulation under the IRC 2018 energy code?
- Blower Door Test Requirements Under IRC 2018
Is a blower door test required, and what ACH number does a new house have to pass?
- Crawl Space Insulation Under IRC 2018 Energy Code
Do I insulate the crawl space walls or the floor above the crawl space under the IRC 2018 energy code?
- Duct Leakage Testing Requirements Under IRC 2018
Do my HVAC ducts need a duct leakage test for the IRC 2018 energy code?
- Energy Certificate Required at Certificate of Occupancy Under IRC 2018
Is an energy certificate required when a new house is completed?
- Energy Code Air Sealing Inspection Checklist Under IRC 2018
What does the inspector look for on the energy code air sealing inspection?
- Energy Code Window-Wall Trade-Offs Under IRC 2018
Can I use better windows to make up for lower wall or attic insulation in the IRC 2018 energy code?
- HVAC Duct Insulation Requirements Outside Conditioned Space Under IRC 2018
What R-value insulation is required for HVAC ducts in an attic, crawl space, garage, or outside conditioned space?
- Insulation R-Values by Climate Zone Under IRC 2018
What R-value insulation do I need for walls, ceilings, floors, basement walls, slabs, and crawl spaces?
- Mechanical Ventilation Requirements for Tight Houses Under IRC 2018
If my house passes the blower door test, do I also need a fresh air system, ERV, HRV, or whole-house ventilation?
- Slab Edge Insulation Requirements Under IRC 2018 Energy Code
When is slab edge insulation required, and how deep does it have to go?
- What Does Continuous Insulation Mean in the IRC 2018 Energy Code?
What does continuous insulation mean in the IRC 2018 energy code?
- Window U-Factor and SHGC Requirements Under IRC 2018
What U-factor and SHGC do my windows and glass doors need for the IRC 2018 energy code?
Have a code question about your project? Get personalized answers from our team — $9/mo.
Membership