How big does a girder or beam need to be under a floor?
Floor Girder and Beam Span Requirements — IRC 2018
Allowable Girder Spans
Published by Jaspector
Code Reference
IRC 2018 — R502.5
Allowable Girder Spans · Floors
Quick Answer
IRC 2018 R502.5 provides Tables R502.5(1) and R502.5(2) for sizing sawn lumber girders and beams supporting floors, based on the span, lumber species, building width, and number of floors carried. A typical built-up 3-ply 2×10 No. 2 Southern Pine girder can span roughly 6 to 10 feet depending on the tributary load. Larger spans or heavier loads require engineered beams.
What R502.5 Actually Requires
Section R502.5 of the IRC 2018 states that girder and beam spans shall not exceed the values in Tables R502.5(1) and R502.5(2). Table (1) covers built-up lumber girders and solid sawn lumber beams supporting one floor. Table (2) covers the same supporting two floors. The tables are organized by building width (20, 28, and 36 feet), girder size (3×, 4×, and built-up 2-ply, 3-ply, 4-ply), lumber species group, and span.
For a 28-foot-wide building (a common residential width), a 3-ply 2×10 No. 2 Hem-Fir built-up girder can span approximately 8 feet 6 inches when supporting one floor. The same girder in Southern Pine can span about 9 feet 6 inches because Southern Pine has higher allowable bending stress. For a 36-foot building (more tributary load), the same girder is reduced to around 7 feet.
Built-up girders made from multiple 2× members must be fastened per the code's nailing requirements — typically two rows of 20d (4-inch) nails at 32 inches on center, staggered between the top and bottom rows, to ensure the individual members act compositely as a single beam.
When the required beam size exceeds what is available in Table R502.5, engineered lumber (LVL, PSL, LSL) is the typical solution. Engineered beam span tables are provided by the manufacturer and governed by ICC-ES evaluation reports rather than R502.5. LVL and PSL beams are common for long spans in open floor plans.
Beams and girders must bear adequately on their supports per R502.6 — minimum 3 inches on concrete or masonry, minimum 1.5 inches on wood posts or steel columns. The beam seat must distribute the load without exceeding the bearing capacity of the support material.
Why This Rule Exists
Girders and beams are the primary structural members in the floor system — everything above them depends on their integrity. An undersized beam deflects excessively, causing floor bounce, sloping floors, cracked drywall in walls below, and sticking doors. In extreme cases, an overloaded beam can fail suddenly. The span tables ensure that selected beam sizes remain within the allowable fiber stress and deflection limits (typically L/360 for live load) that define an acceptable floor structural system.
What the Inspector Checks at Rough and Final
At the framing inspection, girders and beams are checked for:
- Beam size (width × depth) consistent with the approved plans and applicable span table.
- Lumber species and grade — verified by grade stamps on individual members for built-up girders.
- Built-up assembly nailing — correct nail size, spacing, and staggering pattern.
- Bearing length — minimum 3 inches on masonry or concrete, 1.5 inches on wood or steel, with no overhanging or unsupported end conditions.
- Post or column alignment — beam load must transfer directly to a post, lally column, or foundation wall, with no beam end hanging in space.
- Notches or holes in the beam — these reduce capacity and may not comply with R502.8 limits for beams.
What Contractors Need to Know
Always specify lumber species and grade on the framing plan. Using "Doug Fir" generically without a grade leaves the plan reviewer unable to verify span compliance. The species group boundaries in Table R502.5 sometimes split species that are commonly bundled together in lumber supply — verify the table's species group for your specific wood.
LVL beams are specified by the manufacturer in terms of section size and span. When switching from a sawn lumber plan to LVL during construction, verify that the LVL section provides at least equivalent moment of inertia and section modulus to the original design. Do not assume that a 3.5-inch × 9.25-inch LVL has the same capacity as a 3-ply 2×10 — they may be close, but the manufacturer's table is the controlling reference.
Temporary beam supports during construction must be adequate to carry the construction loads. Partially completed floors with workers, equipment, and materials can impose loads well above the 40 psf residential design — do not remove temporary shores prematurely.
Built-up wood beams must be nailed with the code-prescribed pattern to ensure the plies act as a composite section. The nailing requirement produces enough shear transfer between plies to allow the composite beam to achieve the tabulated spans. Beams fastened with a single row of nails or with smaller fasteners at wider spacing will not develop the full composite capacity. Inspect built-up beams before installation to verify nailing. Field-assembled beams should have the nailing documented before installation if the inspector cannot access the beam face after framing is complete.
Engineered lumber beams must be specified by a licensed engineer or sized using manufacturer-provided span tables, not the IRC built-up beam tables. Engineered beams are significantly more efficient than built-up sawn lumber and are appropriate when spans exceed what the built-up table allows or when framing depth is constrained by architectural requirements. Always follow manufacturer installation instructions for engineered beams, including minimum bearing length, end-cap requirements at exterior exposure, and approved connection hardware. Field modifications to engineered lumber, including notching, boring, or cutting the depth, require manufacturer approval and void the design if done without that authorization.
Built-up wood beams must be nailed with the code-prescribed pattern to ensure the plies act as a composite section. The nailing requirement produces enough shear transfer between plies to allow the composite beam to achieve the tabulated spans. Beams fastened with a single row of nails or with smaller fasteners at wider spacing will not develop the full composite capacity. Inspect built-up beams before installation to verify nailing. Field-assembled beams should have the nailing documented before installation if the inspector cannot access the beam face after framing is complete.
Engineered lumber beams must be specified by a licensed engineer or sized using manufacturer-provided span tables, not the IRC built-up beam tables. Engineered beams are significantly more efficient than built-up sawn lumber and are appropriate when spans exceed what the built-up table allows or when framing depth is constrained by architectural requirements. Always follow manufacturer installation instructions for engineered beams, including minimum bearing length, end-cap requirements at exterior exposure, and approved connection hardware. Field modifications to engineered lumber, including notching, boring, or cutting the depth, require manufacturer approval and void the design if done without that authorization.
Built-up wood beams must be nailed with the code-prescribed pattern to ensure the plies act as a composite section. The nailing requirement produces enough shear transfer between plies to allow the composite beam to achieve the tabulated spans. Beams fastened with a single row of nails or with smaller fasteners at wider spacing will not develop the full composite capacity. Inspect built-up beams before installation to verify nailing. Field-assembled beams should have the nailing documented before installation if the inspector cannot access the beam face after framing is complete.
Engineered lumber beams must be specified by a licensed engineer or sized using manufacturer-provided span tables, not the IRC built-up beam tables. Engineered beams are significantly more efficient than built-up sawn lumber and are appropriate when spans exceed what the built-up table allows or when framing depth is constrained by architectural requirements. Always follow manufacturer installation instructions for engineered beams, including minimum bearing length, end-cap requirements at exterior exposure, and approved connection hardware. Field modifications to engineered lumber, including notching, boring, or cutting the depth, require manufacturer approval and void the design if done without that authorization.
What Homeowners Get Wrong
Homeowners who convert a crawl space into a finished room or remove a load-bearing wall in a basement sometimes discover that the existing girder is undersized when the load redistribution analysis is done. What was adequate for one load path may be insufficient after a remodel changes the load configuration. Always have a structural engineer evaluate any beam when load-bearing conditions change.
Another common misunderstanding: "the previous owner put it there and it was fine for 30 years." Long-term satisfactory performance does not mean compliance with current code — and when permits are pulled for a remodel, the existing conditions may need to be brought up to current standards, including beam sizing.
Pocket bearing in masonry or concrete walls requires attention to the beam end condition. A beam seated in a masonry pocket must have clearance on all three sides — both sides and the end — to allow for expansion and prevent the beam from acting as a column within the pocket if the wall settles or the beam expands. The minimum clearance is typically 1/2 inch on each side. The bearing surface within the pocket must also meet the 3-inch minimum bearing requirement of R502.6, measured along the beam length.
State and Local Amendments
IRC 2018 R502.5 span tables are adopted without significant modification in TX, GA, VA, NC, SC, TN, AL, MS, KY, and MO. In humid Gulf Coast climates, pressure-treated lumber is sometimes used for beams in crawl space conditions, and the preservative treatment can slightly affect the allowable stress values. Consult the applicable Southern Pine or species group data for treated lumber allowable values, which may differ from untreated values in Table R502.5.
IRC 2021 did not revise the girder span tables in R502.5 beyond minor formatting improvements. Updated NDS lumber values for some species may affect the underlying calculation basis, but the published table values in 2021 are substantially the same as 2018 for typical species groups.
When to Hire a Licensed Contractor
Girder installation requires precision in bearing seat preparation, post or column alignment, and built-up beam nailing. A licensed framing contractor should perform all beam and girder installation. For any beam longer than what the prescriptive table allows, a licensed structural engineer must size the beam and specify connections. Engineered beam installation also typically requires verification that the posts and columns below are adequate for the increased load — this engineering review is the contractor's responsibility to initiate.
Common Violations Found at Inspection
- Girder size smaller than required by Table R502.5 for the span, building width, and floor count being supported.
- Built-up girder nailing inadequate — using 16d nails instead of 20d, or spacing greater than 32 inches on center.
- Girder bearing less than 3 inches on concrete or masonry foundations — beam set too close to the foundation wall edge.
- Lumber grade not verified — unstamped or mixed-grade members in a built-up girder.
- Beam notched at bearing beyond allowable limits, reducing the effective bearing depth and creating a stress concentration at the notch.
- LVL beam installed without the manufacturer's ESR on file — inspector cannot verify compliance with published span values.
- Single-ply beam where the plan calls for two or three plies — not visible without a close look at the beam cross-section width.
When beam span tables are used for beams that support unequal spans on each side — for example, a beam at the edge of a floor with different joist spans on each side — the load on the beam is the sum of the tributary widths from both sides. Verify that the table lookup accounts for the total tributary width, not just one side, when joist spans differ on each side of the beam.
Frequently Asked Questions
FAQ — Floor Girder and Beam Span Requirements — IRC 2018
- Can I use three 2×10s nailed together as a beam for an 11-foot span?
- Table R502.5 will tell you. For a 28-foot building with one floor, a 3-ply 2×10 No. 2 Southern Pine can span approximately 9 to 9.5 feet. An 11-foot span likely exceeds the table allowable for this size and would require either a larger built-up beam (3-ply 2×12 or 4-ply 2×10) or an engineered LVL beam. Check the specific species and grade in the applicable table.
- Does a steel beam follow the same IRC span table?
- No. Steel beams are not covered by Table R502.5, which addresses only sawn lumber girders and beams. Steel beams must be sized by a licensed structural engineer using steel design standards. However, IRC 2018 does permit the use of steel beams in residential construction — they require engineering calculations rather than prescriptive table compliance.
- What is the minimum bearing for a beam on a wood post?
- R502.6 requires a minimum of 1.5 inches of bearing on wood posts or metal connectors. This is the minimum — the beam end must fully overlap the post by at least 1.5 inches. Most structural details show beam bearing of 3.5 inches (the full width of a 4×4 post) or more for practical reasons.
- How is an LVL beam selected if it is not in the IRC table?
- The manufacturer of the LVL (e.g., Weyerhaeuser, Georgia-Pacific, Boise Cascade) publishes span tables specific to their product in their technical guide. These tables are based on the product's ICC-ES evaluation report (ESR). Specify the LVL size from the manufacturer's table for the given span, load, and supported width, and submit the table and ESR with the permit application.
- Can I splice a built-up girder at a point of zero moment?
- Splices in built-up girders are permitted only at bearing points (directly over a post or column), which is the point of minimum shear stress. Splicing individual members within the span — even with blocking or strapping — reduces the effective section and is generally not permitted under the prescriptive code. Splices in the field span require engineering design.
- What happens if a beam deflects excessively but doesn't fail?
- Excessive deflection (more than L/360 for live load) causes floor bounciness, cracking of interior finishes, and potentially misalignment of doors and windows. While the beam may not fail structurally, the floor system is performing below acceptable standards. An engineer may recommend sistering the beam, adding a mid-span support, or replacing the beam with a stiffer section.
Also in Floors
← All Floors articles- Deck Beam Bearing on Posts — IRC 2018
What does IRC 2018 require for deck beam bearing on posts?
- Deck Joist Span Requirements — IRC 2018
How far can deck joists span under IRC 2018?
- Drilling and Notching Floor Joists — IRC 2018
Can I notch or drill holes in floor joists for plumbing or wiring?
- Floor Joist and Beam Bearing Requirements — IRC 2018
How much bearing do floor joists, beams, or girders need on wood, steel, masonry, or concrete?
- Floor Joist Blocking and Bridging Requirements — IRC 2018
Do floor joists need blocking or bridging at supports?
- Floor Joist Cantilever Limits — IRC 2018
How far can floor joists cantilever past a beam or foundation?
- Floor Joist Span Limits — IRC 2018
How far can floor joists span under the IRC?
- Floor Sheathing Thickness for Joist Spacing — IRC 2018
What thickness subfloor is required for floor joists spaced 16 or 24 inches on center?
- Wood Touching Concrete — Pressure-Treated Requirements — IRC 2018
When does wood touching concrete need to be pressure-treated?
Have a code question about your project? Get personalized answers from our team — $9/mo.
Membership